The parameters for the four step residual overcurrent protection are set via the local
HMI or PCM600. The following settings can be done for the function.
Common base IED values for primary current (
IBase
), primary voltage (
UBase
)
and primary power (
SBase
) are set in the global base values for settings function
GBASVAL.
GlobalBaseSel
: This is used to select GBASVAL function for reference of base
values.
SeqTypeUPol
: This is used to select the type of voltage polarising quantity i.e. Zero
seq and Neg seq for direction detection.
SeqTypeIPol
: This is used to select the type of current polarising quantity i.e. Zero
seq and Neg seq for direction detection.
SeqTypeIDir
: This is used to select the type of operating current quantity i.e. Zero
seq and Neg seq for direction detection.
7.4.3.1
Common settings for all steps
M15282-81 v10
AngleRCA
: Relay characteristic angle given in degree. This angle is defined as
shown in Figure
. The angle is defined positive when the residual current lags
the reference voltage (Upol = 3U
0
or U
2
)
Upol = -3U
0
or
IN>Dir
RCA
Operation
-3U
2
IEC05000135-5-en.vsdx
IEC05000135 V5 EN-US
Figure 51:
Relay characteristic angle given in degree
In a normal transmission network a normal value of RCA is about 65°. The setting
range is -180° to +180°.
1MRK 504 169-UEN A
Section 7
Current protection
Transformer protection RET650 2.2 IEC
123
Application manual
Summary of Contents for ret650
Page 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Page 2: ......
Page 28: ...22...
Page 38: ...32...
Page 42: ...36...
Page 80: ...74...
Page 168: ...162...
Page 174: ...168...
Page 250: ...244...
Page 346: ...340...
Page 366: ...360...
Page 390: ...384...
Page 391: ...385...