
•
magnetizing inrush currents
•
overexcitation magnetizing currents
•
load tap changer
•
external and internal phase faults which do not involve earth
•
symmetrical overload conditions
Due to its features, REFPDIF is often used as a main protection of the transformer
winding for all faults involving earth.
6.2.2.1
Transformer winding, solidly earthed
M13048-3 v10
The most common application is on a solidly earthed transformer winding. The
connection is shown in Figure
IEC09000109-4-EN.vsd
REFPDIF
I3PW1CT1
I3P
IdN/I
Protected
winding
IEC09000109-4-EN V2 EN-US
Figure 34:
Connection of the low impedance Restricted earth fault function
REFPDIF for a directly (solidly) earthed transformer winding
6.2.2.2
Transformer winding, earthed through zig-zag earthing transformer
M13048-8 v10
A common application is for low reactance earthed transformer where the earthing
is through separate zig-zag earthing transformers. The fault current is then limited
to typical 800 to 2000 A for each transformer. The connection for this application
is shown in figure
.
Section 6
1MRK 504 169-UEN A
Differential protection
94
Transformer protection RET650 2.2 IEC
Application manual
Summary of Contents for ret650
Page 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Page 2: ......
Page 28: ...22...
Page 38: ...32...
Page 42: ...36...
Page 80: ...74...
Page 168: ...162...
Page 174: ...168...
Page 250: ...244...
Page 346: ...340...
Page 366: ...360...
Page 390: ...384...
Page 391: ...385...