Table 116:
Fault record data
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.FLTRFRC1
Fault record data
9409
u32
1
.OpCnt.stVal
Fault record number (high)
0..999999
9410
(Low word)
9411
i16
1
.ProFnc.stVal
Protection function
-32768...327
67
9412
u16
100
.Hz.mag
Frequency
30…80.00
[Hz]
9413
u16
100
.StrDur.mag
Start duration
0...100.00 [%]
9414
u32
1000
.StrOpTm.mag
Operate time [ms] (high)
0...999999.99
9
9415
(Low word)
9416
u32
100
.FltPtR.mag
Fault resistance
0.00…
1000000.00
ohms
9417
(Low word)
9418
u32
100
.FltDiskm.mag
Fault distance
0.00…
9999.99 pu
9419
(Low word)
9420
u16
1
.ActSetGr.stVal
Active setting group
1…6
9421
u16
1
.ShotPntr.stVal
AR shot pointer value
0...7
Captured values during fault
9422
u16
1000
.Max50DifAA.mag
Max. diff. current phs A
0.000...80.00
0 [pu]
9423
u16
1000
.Max50DifAB.mag
Max. diff. current phs B
0.000...80.00
0 [pu]
9424
u16
1000
.Max50DifAC.mag
Max. diff. current phs C
0.000...80.00
0 [pu]
9425
u16
1000
.Max50RstAA.mag
Max. bias current phs A
0.000…
50.000 [pu]
9426
u16
1000
.Max50RstAB.mag
Max. bias current phs B
0.000…
50.000 [pu]
9427
u16
1000
.Max50RstAC.mag
Max. bias current phs C
0.000…
50.000 [pu]
9428
u16
1000
.DifAPhsA.mag
Diff. current phs A
0.000...80.00
0 [pu]
9429
u16
1000
.DifAPhsB.mag
Diff. current phs B
0.000...80.00
0 [pu]
9430
u16
1000
.DifAPhsC.mag
Diff. current phs C
0.000...80.00
0 [pu]
9431
u16
1000
.RstAPhsA.mag
Bias current phs A
0.000…
50.000 [pu]
9432
u16
1000
.RstAPhsB.mag
Bias current phs B
0.000…
50.000 [pu]
9433
u16
1000
.RstAPhsC.mag
Bias current phs C
0.000…
50.000 [pu]
Table continues on next page
Section 2
1MRS756878 H
Modbus data mappings
62