1MAC309294-MB F
Section 6
Condition monitoring functions
RER620
365
Technical Manual
Figure 199:
Significance of the
Difference Cor time
setting
The
Difference Cor time
setting is used instead of the auxiliary contact to accumulate the
energy from the time the main contact opens. If the setting is positive, the calculation of
energy starts after the auxiliary contact has opened and when the delay is equal to the value
set with the
Difference Cor time
setting. When the setting is negative, the calculation starts
in advance by the correction time before the auxiliary contact opens.
The accumulated energy outputs
IPOW_A(_B, _C)
are available through the Monitored
data view on the LHMI or through tools via communications. The values can be reset by
setting the parameter
CBCMx acc. energy
setting to true in the clear menu from WHMI or
LHMI.
Alarm limit check
The
IPOW_ALM
alarm is activated when the accumulated energy exceeds the value set
with the
Alm Acc currents Pwr
threshold setting. However, when the energy exceeds the
limit value set with the
LO Acc currents Pwr
threshold setting, the
IPOW_LO
output is
activated.
The
IPOW_ALM
and
IPOW_LO
outputs can be blocked by activating the binary input
BLOCK
.
6.1.4.6
Remaining life of the circuit breaker
Every time the breaker operates, the life of the circuit breaker reduces due to wearing. The
wearing in the breaker depends on the tripping current, and the remaining life of the
breaker is estimated from the circuit breaker trip curve provided by the manufacturer. The
remaining life is decremented at least with one when the circuit breaker is opened.
The operation of the remaining life of the circuit breaker subfunction can be described by
using a module diagram. All the modules in the diagram are explained in the next sections.
Main Contact
POSCLOSE_A
0
1
open
close
Energy
accumulation starts
Difference Cor time
(Negative)
Main Contact
POSCLOSE_A
0
1
open
close
Energy
accumulation starts
Difference Cor time
(Positive)
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......