7.3.15.1
Verifying the settings
SEMOD175058-7 v6
The overpower protection shall be set to values according to the real set values to be used. The
test is made by means of injection of voltage and current where the amplitude of both current
and voltage and the phase angle between the voltage and current can be controlled. During the
test the analog outputs of active and reactive power shall be monitored.
1.
Connect the test set for injection of voltage and current corresponding to the mode to
be used in the application. If a three phase test set is available this could be used for all
the modes. If a single phase current/voltage test set is available the test set should be
connected to a selected input for one phase current and voltage.
Use the formulas stated in
for the different calculation modes used. The set
mode
Mode can be found under Main menu/Settings/IED Settings/Current/
GOPPDOP(32,P>)/GOPPDOP:1/General.
2.
Adjust the injected current and voltage to the set rated values in % of
IBase and UBase
(converted to secondary current and voltage). The angle between the injected current
and voltage shall be set equal to the set direction
Angle1, angle for stage 1 (equal to 0° for
low forward power protection and equal to 180° for reverse power protection). Check
that the monitored active power is equal to 100% of rated power and that the reactive
power is equal to 0% of rated power.
3.
Change the angle between the injected current and voltage to
90°. Check that
the monitored active power is equal to 0% of rated power and that the reactive power is
equal to 100% of rated power.
4.
Change the angle between the injected current and voltage back to
Angle1 value. Increase
the current slowly from 0 until the START1 signal, start of stage 1, is activated. Check the
injected power and compare it to the set value
Power1, power setting for stage 1 in % of
Sbase.
5.
Increase the current to 100% of
IBase and switch the current off.
6.
Switch the current on and measure the time for activation of TRIP1, trip of stage 1.
7.
If a second stage is used, repeat steps
7.3.15.2
Completing the test
SEMOD175058-66 v4
Continue to test another function or end the testing by setting the parameter
TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter
Blocked to No under Main menu/Tests/Function test modes/Current/
GOPPDOP(32,P>)/GOPPDOP:X for the function, or for each individual function in a chain, to be
tested next. Remember to set the parameter
Blocked to Yes, for each individual function that
has been tested.
7.4
Testing voltage protection functions
7.4.1
Two step undervoltage protection UV2PTUV
M13796-2 v6.1.1
Prepare the IED for verification of settings as outlined in the section
.
Values of the logical signals for UV2PTUV are available on the local HMI under Main menu/
Tests/Function status/Voltage/UV2PTUV(27,2U<)/UV2PTUV:1. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.
7.4.1.1
Verifying the setting
Verification of START value and time delay to operate for Step 1
M13796-29 v6
1MRK 505 293-UEN B
Section 7
Testing functionality
Breaker protection REQ650
65
Commissioning manual
© Copyright 2013 ABB. All rights reserved
Summary of Contents for REQ650 1.3 IEC
Page 1: ...Relion 650 SERIES Breaker protection REQ650 Version 1 3 IEC Commissioning manual ...
Page 2: ......
Page 12: ...6 ...
Page 20: ...14 ...
Page 28: ...22 ...
Page 40: ...34 ...
Page 42: ...36 ...
Page 116: ...110 ...
Page 123: ...117 ...