Operation mode 3I
0
· 3U
0
· cosφ
SEMOD175060-76 v6
1.
Set the polarizing voltage to 1.2 ·
UNRel> and the phase angle between voltage and
current to the set characteristic angle (
RCADir), the current lagging the voltage.
2.
Measure that the operate power is equal to the
SN> setting for the set directional
element.
Note that for operation, both the injected current and voltage must be greater than the
set values
INRel> and UNRel> respectively.
The function activates the START and STDIRIN outputs.
3.
Measure with angles
j
=
/- 45° that the measuring element operates when 3I
0
·
3U
0
· cos (
RCADir -
j
) = 3I0 · 3U0 · cos(+/-45) =
SN>.
4.
Compare the result with the set value. Take the set characteristic into consideration, see
5.
Measure the operate time of the timer by injecting 1.2 ·
UNRel> and a current to get two
times the set
SN> operate value.
( )
0
0
/ 3
3
cos
test
test
Tinv
kSN Sref
I
U
j
=
×
×
×
IECEQUATION2403 V1 EN-US
(Equation 2)
6.
Compare the result with the expected value.
The expected value depends on whether definite or inverse time was selected.
7.
Continue to test another function or complete the test by setting the test mode to
Off.
Operation mode 3I
0
and φ
SEMOD175060-87 v6
1MRK 505 293-UEN B
Section 7
Testing functionality
Breaker protection REQ650
51
Commissioning manual
© Copyright 2013 ABB. All rights reserved
Summary of Contents for REQ650 1.3 IEC
Page 1: ...Relion 650 SERIES Breaker protection REQ650 Version 1 3 IEC Commissioning manual ...
Page 2: ......
Page 12: ...6 ...
Page 20: ...14 ...
Page 28: ...22 ...
Page 40: ...34 ...
Page 42: ...36 ...
Page 116: ...110 ...
Page 123: ...117 ...