Reg A Scale
IEC 61850 name
SA name Description
Values
208
Value reported to user with a
scale factor of "1" when
channel configured as
dimensionless and with a scale
factor of "100" when channel
configured as either mA or
RTD
.AnIn1.mag.f
RTD 10-Channel 1 Input Value
-40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
209
.AnIn2.mag.f
RTD 10-Channel 2 Input Value
-40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
210
.AnIn3.mag.f
RTD 10-Channel 3 Input Value
-40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
211
.AnIn4.mag.f
RTD 10-Channel 4 Input Value
-40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
212
<reserved>
<reserved>
0
213
<reserved>
<reserved>
0
214
<reserved>
<reserved>
0
215
<reserved>
<reserved>
0
216
.AnIn1.range/.An
In2.range
RTD 10- Channel Range Information
Channel - 2 (High Byte)
Channel - 1 (Low Byte)
Normal – 0;
High – 1;
Low – 2;
High High – 3;
Low Low – 4;
217
.AnIn3.range/.An
In4.range
RTD 10- Channel Range Information
Channel - 4 (High Byte)
Channel - 3 (Low Byte)
Normal – 0;
High – 1;
Low – 2;
High High – 3;
Low Low – 4;
218
<reserved>
<reserved>
0
219
<reserved>
<reserved>
0
220
<reserved>
<reserved>
0
221
<reserved>
<reserved>
0
222
<reserved>
<reserved>
0
223
<reserved>
<reserved>
0
1) As per the configuration
7.2.8
LD0.RTDGGIO RTD channel range information
RTD input channel range information can be accessed with addresses listed in the
table.
Section 7
1MRS757488 H
Modbus TCP communication
202
RIO600
Installation and Commissioning Manual