
32
R E M 61 5 A N S I 5.0 FP1
M OTO R P R OT EC T I O N A N D CO N T R O L
—
Table 36. Three-phase undervoltage protection (PHPTUV)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±2 Hz
±1.5% of the set value or ±0.002 x U
n
Start time
1) 2)
Minimum
Typical
Maximum
U
Fault
= 0.9 x set Start value 62 ms
66 ms
70 ms
Reset time
Typically 40 ms
Reset ratio
Depends on the set Relative hysteresis
Retardation time
< 35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms3)
Suppression of harmonics
DFT: -50dB at f = n x f
n
, where n = 2, 3, 4, 5,…
1) Start value = 1.0 × U
n
, Voltage before fault = 1.1 × U
n
, f
n
= 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Minimum Start value = 0.50, Start value multiples in range of 0.90...0.20
1) For further reference, see the Operation characteristics table
—
Table 37. Three-phase undervoltage protection (PHPTUV) main settings
Parameter
Function
Value (range)
Step
Start value
PHPTUV
0.05...1.20 × U
n
0.01
Time multiplier
PHPTUV
0.05...15.00
0.01
Operate delay time
PHPTUV
60...300000 ms
10
Operating curve type
1)
PHPTUV
Definite or inverse time
Curve type: 5, 15, 21, 22, 23
—
Table 38. Positive-sequence undervoltage protection (PSPTUV)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±2 Hz
±1.5% of the set value or ±0.002 x I
n
Start time
(1), (2)
Minimum
Typical
Maximum
U
Fault
= 0.99 x set Start value
U
Fault
= 0.9 x set Start value
52 ms
44 ms
55 ms
47 ms
58 ms
50 ms
Reset time
Typically 40 ms
Reset ratio
Depends on the set Relative hysteresis
Retardation time
< 35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50dB at f = n x f
n
, where n = 2, 3, 4, 5,…
1 Start value = 1.0 × U
n
, positive-sequence voltage before fault = 1.1 × U
n
, f
n
= 50 Hz, positive sequence undervoltage with nominal frequency injected from random phase angle, results
based on statistical distribution of 1000 measurements
2 Includes the delay of the signal output contact
—
Table 39. Positive-sequence undervoltage protection (PSPTUV) main settings
Parameter
Function
Value (range)
Step
Start value
PSPTUV
0.010...1.200 × U
n
0.001
Operate delay time
PSPTUV
40...120000 ms
10
Voltage block value
PSPTUV
0.01...1.00 × U
n
0.01