PCM600 Event Viewer can be used to view the audit trail events and process related
events. Audit trail events are visible through dedicated Security events view. Since
only the administrator has the right to read audit trail, authorization must be used
in PCM600. The audit trail cannot be reset, but PCM600 Event Viewer can filter data.
Audit trail events can be configured to be visible also in WHMI Event list together
with process related events.
To expose the audit trail events through Event list, define the
Authority
logging level parameter via Configuration > Authorization > Security.
This exposes audit trail events to all users.
Table 5: Comparison of authority logging levels
Audit trail event
Authority logging level
None
Configuration
change
Settings edit
All
Configuration change
●
●
●
Firmware change
●
●
●
Firmware change fail
●
●
●
Attached to retrofit test case
●
●
●
Removed from retrofit test case
●
●
●
Control remote
●
●
Test on
●
●
Test off
●
●
Reset trips
●
●
Time change
●
View audit log
●
Login
●
Logout
●
Password change
●
Firmware reset
●
Violation local
●
Violation remote
●
2.7
Communication
The merging unit supports a range of communication protocols including IEC
61850 and IEC 61850-9-2 LE. Operational information and controls are available
SMU615 overview
1MRS758580 C
22
SMU615
Application Manual