3.3
Application configuration A
3.3.1
Applications
The application configuration A is mainly intended for sharing currents and voltages
over the process bus in the digital MV switchgear (main or backup).
The merging unit with an application configuration is delivered from the factory
with default settings and parameters. The end-user flexibility for incoming,
outgoing and internal signal designation within the merging unit enables this
configuration to be further adapted to different primary circuit layouts and the
related functionality needs by modifying the internal functionality using PCM600.
3.3.2
Functions
3.3.2.1
Default I/O connections
Connector pins for each input and output are presented in the Merging unit's
physical connections section.
Table 8: Default connections for analog inputs with AIM0013
Analog input
Default usage
Connector pins
IL1
Phase A current IL1
X120:7,8
IL2
Phase B current IL2
X120:9,10
IL3
Phase C current IL3
X120:11,12
Io
Residual current
X120:13,14
U1
Phase-to-earth voltage UL1
X120:1,2
U2
Phase-to-earth voltage UL2
X120:3,4
U3
Phase-to-earth voltage UL3
X120:5,6
Table 9: Default connections for analog inputs with SIM0002
Analog input
Default usage
Connector pins
IL1
Phase A current IL1
X131:4,5
IL2
Phase B current IL2
X132:4,5
IL3
Phase C current IL3
X133:4,5
Io
Residual current
X130:1,2
Table continues on the next page
1MRS758580 C
Merging unit variants
SMU615
Application Manual
39