Detailed information regarding the IEC 61850 implementation of the IED is
described inside the conformance documents.
•
MICS, Modeling Information Conformance Statement, contains the
declaration of the used logical node types.
•
PICS, Protocol Information Conformance Statement, contains the details and
what is supported regarding protocol facilities.
•
PIXIT, Protocol Extra Information, contains additional information on how the
IEC 61850 is implemented and used.
•
TICS, Tissue Information Conformance Statement, contains the supported
Tissues, which are handled in the Tissues process as defined by UCA, Utility
Communication Architecture forum. The Tissues handling is found in http://
www.tissue.iec61850.com.
The conformance documents are unique for each product release and refer to each
other. The identities included in the related documents refer to a specific version of
the IED series.
The communication profile in IEC 61850 uses the MMS standard, which uses
Ethernet and TCP/IP to handle the information transport within the substation.
The data modelling uses the concept of logical nodes to identify the published
information for communication. The standard defines a set of logical nodes, each
representing a communication view of a process function with a number of data
objects. For example, a transformer differential - or line differential protection,
because the standard defines only a differential protection. Therefore, it is possible
to adapt the logical node, which is defined in the standard, as a logical node class.
The standard defines methods to describe the actually used logical node as a logical
node type which is then based upon the logical node class. This allows all partners
to interpret the logical node type information because the description is completely
given in the standard. The type description of all logical nodes is part of the Data
Type Template (DTT) section in the SCL description file of a station or the IED.
Besides the information about the configuration of the communication facilities,
this manual contains the full description of all logical nodes available in the IEDs.
The information about the logical nodes and their data objects may be used to
identify which signals are available for the functions as described in the technical
manual. The link to the technical manual is done in the logical node tables by
listing the signal name as given in the function block, or as seen in PCM600 or the
LHMI.
2.2
Related documentation to IEC 61850
GUID-906D4C7F-29FD-4922-8A8B-8A3A3E2B811E v7
Use the latest revision of the documents listed, unless stated otherwise.
Section 2
1MRK 511 440-UEN A
Introduction to IEC 61850
12
Switchgear control unit SAM600-IO Version 2.2 IEC
Communication protocol manual