reoccurs during the reset time, the operation calculation is made based on the
effects of the period when
START
was previously active. This is intended to allow an
operating condition to occur in less time to account for the heating effects from the
previous active start period.
When
START
becomes active, the reset time is based on the following equation.
reset time
START
DUR
Cooling time
=
⋅
_
100
(Equation 248)
For the IDMT curves, when
START
is deactivated, the integral value calculated during
START
is continuously decremented by a constant that causes its value to become
zero when the reset time elapses during the reset period. If a fault reoccurs, the
integration continues from the current integral value and the start time is adjusted,
as shown in
. The start time becomes the value at the time when the
fault dropped off minus the amount of reset time that occurred. If the reset period
elapses without a fault being detected, the saved values of the start time and
integration are cleared.
Figure 496: An example of a delayed reset in the inverse time characteristics.
When the start becomes active during the reset period, the operate time counter
continues from the level corresponding to the drop-off (reset time = 0.50 · Cooling
time)
Overexcitation IDMT curves 1, 2 and 3
The base equation for the IDMT curves "OvExt IDMT Crv1", "OvExt IDMT Crv2" and
"OvExt IDMT Crv3" is:
t s
e
ak b
M
c
( )
=
⋅
+ −
60
100
(Equation 249)
Protection functions
1MRS759142 F
890
REX640
Technical Manual