9.12.5.1
Voltage monitoring
Voltage monitoring module calculates measurement values necessary in HSABTC
internal operation. Functionally module can be split to submodules presented in
. Each module is explained later below.
U3P1
U3P2
U3P_BB
U_AB_1
U_BC_1
U_CA_1
U_AB_2
U_BC_2
U_CA_2
U_AB_BB
FRQ_MEAS_1
FRQ_MEAS_2
FRQ_MEAS_BB
ANG_DIFF_1
Amplitude
calculation
Frequency
calculation
Angle
calculation
ANG_DIFF_2
F1_U_A_AB
F1_U_B_BC
F1_U_C_CA
F2_U_A_AB
F2_U_B_BC
F2_U_C_CA
BB_U_A_AB
Figure 933: Voltage monitoring module diagram.
Amplitude calculation
Amplitude calculation reports phase-to-phase voltages from busbar (U_AB_BB),
feeder 1 (U_AB_1, U_BC_1, U_CA_1) and feeder 2 (U_AB_2, U_BC_2, U_CA_2).
Frequency calculation
This module calculates the frequencies of feeder 1, feeder 2 and busbar. The
calculated frequencies for feeder 1, feeder 2 and busbar, FRQ_MEAS_1, FRQ_MEAS_2
and FRQ_MEAS_BB respectively, are available as function outputs.
Angle calculation
This module calculates phase angle difference between feeder 1 and busbar
(ANG_DIFF_1), and between feeder 2 and busbar (ANG_DIFF_2). Values are available
in monitored data view.
9.12.5.2
Transfer direction
The module checks the present transfer direction and stores the valid saved transfer
direction from the breaker’s auxiliary contact states. Functionally module can be
split to submodules presented in
. Each module is explained later below.
1MRS759142 F
Control functions
REX640
Technical Manual
1763