![ABB RELION REX640 Installation Manual Download Page 72](http://html.mh-extra.com/html/abb/relion-rex640/relion-rex640_installation-manual_3045255072.webp)
1
2
1
Light gray pairs with short circuit
facility (CT), RAL7035
2
Dark gray pairs without short
circuit facility (VT), RAL7042
Figure 64: Identifying CT/VT color coding
1
CT connector coding
2
VT connector coding
3
Empty connector
Figure 65: Loose CT/VT connector coding
1
CT connector coding
2
VT connector coding
3
Empty connector
Figure 66: Fixed CT/VT connector coding
5.4.1
Connecting current and voltage inputs
Conventional instrument transformers
Each terminal for CTs/VTs is dimensioned for one 0.5...6.0 mm
2
(AWG 20-10) wire or
for two wires of maximum 2.5 mm
2
(AWG 14).
Connecting