vl im vb im xline il re rline il im
=
-
×
-
×
EQUATION2085-ANSI V1 EN
(Equation 110)
where:
vb
is the complex value of the busbar voltage
il
is the complex value of the line current (secondary side)
rline
is the value of the line resistance
xline
is the value of the line reactance
For comparison with the set-point value, the modulus of U
L
are according to
.
¦ V
L
¦ = (vl , re)
2
+ (vl , im)
2
EQUATION2087-ANSI V2 EN
(Equation 111)
4.
Inject voltage for V
B
equal to setting
VSet
.
5.
Inject current equal to rated current
I2Base
.
6.
Confirm on the local HMI that service values for bus voltage and load current are
equal to injected quantities.
7.
Confirm that the calculated value for load voltage, displayed on the local HMI, is
equal to that derived through hand calculations.
8.
When setting
OperationLDC
set to
Enabled
, the voltage regulation algorithm uses
the calculated value for load voltage as the regulating quantity to compare against
VSet
and the voltage deadband limits
VDeadband
and
VDeadbandInner
.
9.
While injecting rated current
I2Base
into the IED, inject a quantity for V
B
that is
slightly higher then
VSet
+ |(
Rline
+j
XLine
) · I
L
|. This will ensure that the regulating
voltage V
L
is higher than
VSet
, and hence no tap change command should be issued
from the IED.
10. Reduce the injected voltage for V
B
slightly below
VSet
+ |(
Rline
+j
XLine
) · I
L
| and
confirm that the calculated value for load voltage is below
VSet
and a tap change
command is issued from the IED.
11.10.3.8
Parallel voltage regulation
Master follower voltage regulation
1.
For the transformers connected in the parallel group, confirm that
OperationPAR
is
set to
MF
.
2.
For parallel operation, it is also recommended to confirm for parallel group
membership, defined by setting
TnRXOP
in the local HMI under
Main menu/
1MRK 504 165-UUS -
Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI
253
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...