WA1 (A)
WA2 (B)
189
189G
289G
989G
689
989
289
189G
289G
389G
689
389G
6289
6189
189G
289G
989G
989
BH_LINE_A
BH_LINE_B
BH_CONN
en04000513_ansi.vsd
152
152
152
ANSI04000513 V1 EN-US
Figure 361:
Switchyard layout breaker-and-a-half
M13570-7 v4
Three types of interlocking modules per diameter are defined. BH_LINE_A (3) and
BH_LINE_B (3) are the connections from a line to a busbar. BH_CONN (3) is the
connection between the two lines of the diameter in the breaker-and-a-half switchyard
layout.
M13569-4 v4
For a breaker-and-a-half arrangement, the modules BH_LINE_A, BH_CONN and
BH_LINE_B must be used.
15.3.9.2
Configuration setting
M13569-6 v5
For application without 989 and 989G, just set the appropriate inputs to open state and
disregard the outputs. In the functional block diagram, 0 and 1 are designated
0=FALSE and 1=TRUE:
•
989_OP = 1
•
989_CL = 0
•
989G_OP = 1
•
989G_CL = 0
1MRK 504 163-UUS A
Section 15
Control
Transformer protection RET670 2.2 ANSI
753
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...