en04000503_ansi.vsd
Section 1
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
BH_LINE
(WA1)A1
(WA2)B1
B2
A2
BH_LINE
BH_LINE
BH_LINE
ANSI04000503 V1 EN-US
Figure 350:
Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic is the same as for the logic for the double-breaker
configuration.
Signal
S1DC_OP
All disconnectors on bus-section 1 are open.
S2DC_OP
All disconnectors on bus-section 2 are open.
VPS1_DC
The switch status of disconnectors on bus-section 1 is valid.
VPS2_DC
The switch status of disconnectors on bus-section 2 is valid.
EXDU_BB
No transmission error from breaker and a half (BH) that contains the above
information.
15.3.7
Interlocking for busbar grounding switch BB_ES (3)
IP14164-1 v4
15.3.7.1
Application
M15015-3 v7
The interlocking for busbar grounding switch (BB_ES, 3) function is used for one
busbar grounding switch on any busbar parts according to figure
89G
en04000504.vsd
ANSI04000504 V1 EN-US
Figure 351:
Switchyard layout BB_ES (3)
M15053-4 v4
The signals from other bays connected to the module BB_ES are described below.
Section 15
1MRK 504 163-UUS A
Control
744
Transformer protection RET670 2.2 ANSI
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...