15.3.6
Interlocking for bus-section disconnector A1A2_DC (3)
IP14159-1 v2
15.3.6.1
Application
M13544-3 v7
The interlocking for bus-section disconnector (A1A2_DC, 3) function is used for one
bus-section disconnector between section 1 and 2 according to figure
. A1A2_DC
(3) function can be used for different busbars, which includes a bus-section
disconnector.
WA1 (A1)
WA2 (A2)
189G
289G
A1A2_DC
en04000492_ansi.vsd
52
ANSI04000492 V1 EN-US
Figure 339:
Switchyard layout A1A2_DC (3)
M13542-4 v4
The signals from other bays connected to the module A1A2_DC are described below.
15.3.6.2
Signals in single breaker arrangement
M13542-6 v5
If the busbar is divided by bus-section disconnectors, the condition
no other
disconnector connected to the bus-section
must be made by a project-specific logic.
The same type of module (A1A2_DC) is used for different busbars, that is, for both
bus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC, corresponding
signals from busbar B are used.
en04000493_ansi.vsd
Section 1
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
ABC_LINE
ABC_BC
ABC_LINE
(WA1)A1
(WA2)B1
(WA7)C
C
B3
A3
AB_TRAFO
AB_TRAFO
A2
B2
ANSI04000493 V1 EN-US
Figure 340:
Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
1MRK 504 163-UUS A
Section 15
Control
Transformer protection RET670 2.2 ANSI
737
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...