en08000358.vsd
IEC08000358 V1 EN-US
Figure 292:
Short-time unbalanced current capability of direct cooled generators
Continuous I
2
- capability of generators is also covered by the standard. Table
below
(from ANSI standard C50.13) contains the suggested capability:
Table 47:
Continous I
2
capability
Type of generator
Permissible I
2
(in percent of rated
generator current)
Salient Pole:
with damper winding
10
without damper winding
5
Cylindrical Rotor
Indirectly cooled
10
Directly cooled
to 960 MVA
8
961 to 1200 MVA
6
1201 to 1500 MVA
5
As it is described in the table above that the continuous negative sequence current
capability of the generator is in range of 5% to 10% of the rated generator current.
During an open conductor or open generator breaker pole condition, the negative
sequence current can be in the range of 10% to 30% of the rated generator current.
Other generator or system protections will not usually detect this condition and the
only protection is the negative sequence overcurrent protection.
Negative sequence currents in a generator may be caused by:
•
Unbalanced loads such as
1MRK 504 163-UUS A
Section 9
Current protection
Transformer protection RET670 2.2 ANSI
603
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...