Ensure that the underreaching zones from both line ends will overlap a sufficient
amount (at least 10%) in the middle of the protected circuit.
8.12.2.7
Tapped line application
GUID-740E8C46-45EE-4CE8-8718-9FAE658E9FCE v1
GUID-7AA566A4-B6E9-41A7-9927-4DAB50BE8D1A v1
C
A
B
BC
ANSI05000224-2-en.vsd
ANSI05000224 V2 EN-US
Figure 183:
Example of tapped line with Auto transformer
This application gives rise to similar problem that was highlighted in section
, that is increased measured impedance due to fault current
infeed. For example, for faults between the T point and B station the measured
impedance at A and C will be
Section 8