max
3
S
ILoad
VLmn
=
×
EQUATION1615-ANSI V1 EN-US
(Equation 195)
where:
Smax
is the maximal apparent power transfer during emergency conditions and
VLmn
is the phase-to-phase voltage during the emergency conditions at the IED location.
8.8.3.1
Load encroachment
SEMOD154782-39 v4
The load encroachment function has two setting parameters,
RLd
for the load
resistance and
LdAngle
for the inclination of the load sector (see figure
).
R
X
RLdFw
RLdRv
LdAngle
LdAngle
LdAngle
ANSI10000192_1_en.vsd
LdAngle
ANSI10000192 V1 EN-US
Figure 149:
Load encroachment characteristic
The calculation of the apparent load impedance Z
load
and minimum load impedance
Z
loadmin
can be done according to equations:
min
max
3 I
V
Zload
=
×
EQUATION1754-ANSI V1 EN-US
(Equation 196)
1MRK 504 163-UUS A
Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI
319
Application manual