The output signal AI1 to AI4 are direct output of the, in SMT, connected input to
GRPx_A, GRPxB, GRPxC and GRPx_N, x=1-12. AIN is always calculated residual
sum from the first three inputs. A3P is grouped, three-phase information containing all
relevant information about four connected inputs. Note that all other functions, with a
few exceptions, use this output in configuration. Note that the SMAI function will
always calculate the residual sum of current/voltage if the input GRPxN is not
connected in SMT. Applications with a few exceptions shall always be connected to
AI3P.
22.9.5.1
Frequency values
GUID-B494B93C-B5AA-4FD6-8080-8611C34C2AD8 v5
The SMAI function includes a functionality based on the level of positive sequence
voltage,
MinValFreqMeas
, to validate if the frequency measurement is valid or not. If
the positive sequence voltage is lower than
MinValFreqMeas
, the function freezes the
frequency output value for 500 ms and after that the frequency output is set to the
nominal value. A signal is available for the SMAI function to prevent operation due to
non-valid frequency values.
MinValFreqMeas
is set as % of
VBase
/√3
If SMAI setting
ConnectionType
is
Ph-Ph
, at least two of the inputs GRPx_A,
GRPx_B and GRPx_C, where 1≤x≤12, must be connected in order to calculate the
positive sequence voltage. Note that phase to phase inputs shall always be connected as
follows: A-B to GRPxA, B-C to GRPxB, C-A to GRPxC. If SMAI setting
ConnectionType
is
Ph-N
, all three inputs GRPx_A, GRPx_B and GRPx_C must be
connected in order to calculate the positive sequence voltage.
If only one phase-phase voltage is available and SMAI setting
ConnectionType
is
Ph-
Ph
, the user is advised to connect two (not three) of the inputs GRPx_A, GRPx_B and
GRPx_C to the same voltage input as shown in figure
to make SMAI calculate a
positive sequence voltage.
SMAI1
BLOCK
DFTSPFC
REVROT
^GRP1_A
^GRP1_B
^GRP1_C
^GRP1_N
SPFCOUT
G1AI3P
G1AI1
G1AI2
G1AI4
G1N
NEUTRAL
PHASEC
PHASEB
PHASEA
VAB
SAPTOF
V3P*
BLOCK
BLKTRIP
TRIP
PICK UP
BLKDMAGN
FREQ
TRM_40.CH7(U)
SAPTOF(1)_TRIP
ANSI10000060-1-en.vsdx
ANSI10000060 V1 EN-US
Figure 303:
Connection example
The above described scenario does not work if SMAI setting
ConnectionType
is
Ph-N
. If only one phase-ground voltage is available,
1MRK 511 408-UUS A
Section 22
Basic IED functions
Phasor measurement unit RES670 2.2 ANSI
791
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...