Y = Magnitude of the Measured Quantity
IEC05000657 V3 EN-US
Figure 197:
Presentation of operating limits
Each analog output has one corresponding supervision level output (X_RANGE). The
output signal is an integer in the interval 0-4 (0: Normal, 1: High limit exceeded, 3:
High-high limit exceeded, 2: below Low limit and 4: below Low-low limit).
The logical value of the functional output signals changes according to figure
The user can set the hysteresis (
XLimHyst
), which determines the difference between
the operating and reset value at each operating point, in wide range for each measuring
channel separately. The hysteresis is common for all operating values within one
channel.
Actual value of the measured quantity
SEMOD54417-150 v4
The actual value of the measured quantity is available locally and remotely. The
measurement is continuous for each measured quantity separately, but the reporting of
the value to the higher levels depends on the selected reporting mode. The following
basic reporting modes are available:
•
Cyclic reporting (
Cyclic
)
•
Magnitude dead-band supervision (
Dead band
)
•
Integral dead-band supervision (
Int deadband
)
•
Amplitude Deadband and 5s cyclic
•
Amplitude Deadband and 30s cyclic
•
Amplitude Deadband and 1min cyclic
Section 16
1MRK 511 408-UUS A
Monitoring
512
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...