SYNCH signal on the MUx function block indicates that protection functions
are blocked due to loss of internal time synchronization to the IED. Since
SyncLostMode
is set to
No block
, this signal is not set.
•
MUSYNCH signal on the MUx function block is set if the datastream
indicates time synchronization loss. However, protection functions are not
blocked.
To get higher availability in protection functions, it is possible to avoid blocking
during time synchronization loss if there is a single source of analog data. This
means that if there is only one physical MU and no TRM, parameter
SyncLostMode
is set to
No block
but parameter
HwSyncSrc
is still set to
PPS
. This maintains
analog and binary data correlation in disturbance recordings without blocking
protection functions if PPS is lost.
18.3.3
IEC 61850 quality expander QUALEXP
GUID-9C5DC78E-041B-422B-9668-320E62B847A2 v1
The quality expander component is used to display the detailed quality of an
IEC/UCA 61850-9-2LE analog channel. The component expands the channel
quality output of a Merging Unit analog channel received in the IED as per the IEC
61850-7-3 standard. This component can be used during the ACT monitoring to get
the particular channel quality of the Merging Unit.
depicts the usage of the quality expander block in ACT.
IEC16000073-1-en.vsdx
IEC16000073 V1 EN-US
Figure 185:
Quality expander block in ACT
The expanded quality bits are visible on the outputs as per IEC 61850-7-3 standard.
When written to IED, the configuration will show the expanded form of the
respective MU channel quality information during the online monitoring in the
ACT.
The quality expander function is intended for monitoring purposes,
not for being used in a logic controlling the behaviour of the
protection or control functions in the IED. The function outputs are
updated once every second and, therefore, do not reflect the quality
bits in real time.
Section 18
1MRK 506 375-UEN A
Station communication
438
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...