Table 37:
Output signals
Name of OUTx
Type
Description
Value when
activated
Value when
deactivated
OUT1
BOOLEAN
Output 1
1
0
OUT2
BOOLEAN
Output 2
2
0
OUT3
BOOLEAN
Output 3
4
0
OUT4
BOOLEAN
Output 4
8
0
OUT5
BOOLEAN
Output 5
16
0
OUT6
BOOLEAN
Output 6
32
0
OUT7
BOOLEAN
Output 7
64
0
OUT8
BOOLEAN
Output 8
128
0
OUT9
BOOLEAN
Output 9
256
0
OUT10
BOOLEAN
Output 10
512
0
OUT11
BOOLEAN
Output 11
1024
0
OUT12
BOOLEAN
Output 12
2048
0
OUT13
BOOLEAN
Output 13
4096
0
OUT14
BOOLEAN
Output 14
8192
0
OUT15
BOOLEAN
Output 15
16384
0
OUT16
BOOLEAN
Output 16
32768
0
The sum of the numbers in column “Value when activated” when all OUTx
(1≤x≤16) are active equals 65535. This is the highest integer that can be converted
by the ITBGAPC function block.
14.12
Elapsed time integrator with limit transgression and
overflow supervision TEIGAPC
14.12.1
Identification
GUID-1913E066-37D1-4689-9178-5B3C8B029815 v3
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2 device
number
Elapsed time integrator
TEIGAPC
-
-
14.12.2
Application
GUID-B4B47167-C8DE-4496-AEF1-5F0FD1768A87 v2
The function TEIGAPC is used for user-defined logics and it can also be used for
different purposes internally in the IED. An application example is the integration
of elapsed time during the measurement of neutral point voltage or neutral current
at earth-fault conditions.
1MRK 506 375-UEN A
Section 14
Logic
Railway application RER670 2.2 IEC
373
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...