IBase
ISet
DI
prim
/
)
100
(
IECEQUATION216 V1 EN-US
The voltage threshold
UPh>
is used to identify low voltage condition in the
system. Set
UPh>
below the minimum operating voltage during emergency
conditions. A safety margin of approximately 70% of
UBase
is recommended.
The current threshold
IPh>
should be set lower than the
IMinOp
for the distance
protection function. A safety margin of 5–10% lower value is recommended.
The setting
INDeblock
is used to block or deblock the underimpedance protection
if residual current exists during fuse failure conditions in the voltage measuring
circuit.
The residual current threshold
2I0<
should be set above the maximum occurring
residual current during normal loading conditions.
The timer
tIN
is used to delay the deblocking of underimpedance protection
functions if required. A default value of 5.0 s is given.
11.2.3.2
Dead line detection
GUID-F5BB1753-B036-49AB-8D0A-7AD377F507C3 v1
The condition for operation of the dead line detection is set by the parameters
IDLD<
for the current threshold and
UDLD<
for the voltage threshold.
Set the
IDLD<
with a sufficient margin below the minimum expected load current.
A safety margin of at least 15-20% is recommended. The operate value must
however exceed the maximum charging current of an overhead line, when only one
phase is disconnected (mutual coupling to the other phases).
Set the
UDLD<
with a sufficient margin below the minimum expected operating
voltage. A safety margin of at least 15% is recommended.
11.2.4
Sudden current and voltage change
GUID-285E48A3-A4ED-475F-B21C-3C543849CAF3 v1
Several instances of FRWSPVC function are available. Therefore if required by
application, one instance of this function can also be used for sudden current and
voltage change detection. This information, for example, can be used in IED
configuration logic to enable higher distance protection zones for catenary
applications.
Section 11
1MRK 506 375-UEN A
Secondary system supervision
210
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...