it is a useful function in circuits for local or remote automation processes in the
power system.
9.1.3
Setting guidelines
M13851-3 v9
All the voltage conditions in the system where U2RWPTUV performs its functions
should be considered. The same also applies to the associated equipment, its
voltage and time characteristic.
There are wide applications where general undervoltage functions are used. All
voltage related settings are made as a percentage of the global base value
UBase
and base current
IBase
, which normally is set to the primary rated voltage level
(phase-to-phase) of the power system or the high voltage equipment under
consideration.
The setting for U2RWPTUV is normally not critical, since there must be enough
time available for the main protection to clear short circuits and earth faults.
Some applications and related setting guidelines for the voltage level are described
in the following sections.
9.1.3.1
Disconnected equipment detection
M13851-53 v3
The setting must be below the lowest occurring "normal" voltage and above the
highest occurring voltage, caused by inductive or capacitive coupling, when the
equipment is disconnected.
9.1.3.2
Power supply quality
M13851-56 v3
The setting must be below the lowest occurring "normal" voltage and above the
lowest acceptable voltage, due to regulation, good practice or other agreements.
9.1.3.3
Voltage instability mitigation
M13851-59 v3
This setting is very much dependent on the power system characteristics, and
thorough studies have to be made to find the suitable levels.
9.1.3.4
Backup protection for power system faults
M13851-62 v3
The setting must be below the lowest occurring "normal" voltage and above the
highest occurring voltage during the fault conditions under consideration.
9.1.3.5
Settings for two step undervoltage protection
M13851-65 v14
Parameters for U2RWPTUV application function are set via local HMI or
Protection and Control Manager PCM600.
Section 9
1MRK 506 375-UEN A
Voltage protection
196
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...