Recloser Protection and Control RER615

IEC 60870-5-101/104 Point List Manual

Summary of Contents for Relion RER615

Page 1: ...Relion product family Grid Automation Recloser Protection and Control RER615 IEC 60870 5 101 104 Point List Manual...

Page 2: ......

Page 3: ...Document ID 1MRS757824 Issued 2015 03 06 Revision C Product version 1 1 Copyright 2015 ABB All rights reserved...

Page 4: ...s document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of the ABB Group All o...

Page 5: ...ted and communicate data and information via a network interface which should be connected to a secure network It is the sole responsibility of the person or entity responsible for network administrat...

Page 6: ...rning electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standards EN...

Page 7: ...Phase overcurrent protection instantaneous stage 1 17 LD0 FDPHLPDOC1 FA Directional phase overcurrent protection low stage 1 17 LD0 FDPHLPDOC2 FA Directional phase overcurrent protection low stage 2 1...

Page 8: ...rvoltage protection 3 24 LD0 PHPTOV1 Phase overvoltage protection 1 24 LD0 PHPTOV2 Phase overvoltage protection 2 25 LD0 PHPTOV3 Phase overvoltage protection 3 25 LD0 PSPTUV1 Positive sequence undervo...

Page 9: ...34 LD0 MVGAPC1 Multipurpose binary inputs 1 34 LD0 MVGAPC2 Multipurpose binary inputs 2 35 LD0 SPCGGIO1 Multipurpose binary output states 1 35 LD0 SPCGGIO2 Multipurpose binary output states 2 36 LD0...

Page 10: ...t breaker condition monitoring 1 48 DR RDRE1 Disturbance recorder 1 48 LD0 SRGAPC1 Multipurpose binary output flipflop resets 1 48 LD0 SRGAPC2 Multipurpose binary output flipflop resets 2 48 LD0 SPCGG...

Page 11: ...anual addresses the communication system engineer or system integrator responsible for pre engineering and engineering for communication setup in a substation from an IED perspective The system engine...

Page 12: ...st manual GUID 7414985D 2433 46E4 B77B CCE64F6FC8D0 V1 EN Figure 1 The intended use of documents during the product life cycle Product series and product specific manuals can be downloaded from the AB...

Page 13: ...performance leading to personal injury or death Therefore comply fully with all warning and caution notices 1 4 2 Document conventions A particular convention may not be used in this manual Abbreviati...

Page 14: ...Io 1 51N 1 1 Non directional earth fault protection high stage instance 1 EFHPTOC1 Io 1 51N 2 1 Non directional earth fault protection instantaneous stage instance 1 EFIPTOC1 Io 1 50N 51N 1 Direction...

Page 15: ...e 1 PSPTUV1 U1 1 47U 1 Negative sequence overvoltage protection instance 1 NSPTOV1 U2 1 47O 1 Frequency protection instance 1 FRPFRQ1 f f df dt 1 81 1 Frequency protection instance 2 FRPFRQ2 f f df dt...

Page 16: ...CBCM 1 CBCM 1 Trip circuit supervision instance 1 TCSSCBR1 TCS 1 TCM 1 Trip circuit supervision instance 2 TCSSCBR2 TCS 2 TCM 2 Fuse failure supervision instance 1 SEQRFUF1 FUSEF 1 60 1 Runtime count...

Page 17: ...n 8 pcs instance 1 TONGAPC1 TON 1 TON 1 Time delay on 8 pcs instance 2 TONGAPC2 TON 2 TON 2 Set reset 8 pcs instance 1 SRGAPC1 SR 1 SR 1 Set reset 8 pcs instance 2 SRGAPC2 SR 2 SR 2 Move 8 pcs instanc...

Page 18: ...12...

Page 19: ...ction high stage DPHHPDOC 1 3 1 3 Non directional earth fault protection low stage FEFLPTOC 1 4 5 1 4 5 Non directional earth fault protection high stage EFHPTOC 1 4 5 1 4 5 Non directional earth faul...

Page 20: ...heck SECRSYN 1 Condition monitoring and supervision Circuit breaker condition monitoring SSCBR 1 1 Trip circuit supervision TCSSCBR 2 2 Fuse failure supervision SEQRFUF 1 1 Runtime counter for machine...

Page 21: ...ption when directional OC and directional EF are chosen Admittance based EF Wattmetric based EF or Harmonics based EF 9 Uo calculated is always used with the first instance 10 UoB calculated is always...

Page 22: ...1 In Use 1 40004 ActSG stVal SG4 Setting group 3 in use 1 In Use 1 40005 ActSG stVal SG5 Setting group 4 in use 1 In Use 1 40006 ActSG stVal SG6 Setting group 5 in use 1 In Use 2 3 3 LD0 FPHLPTOC1 FA...

Page 23: ...A name Description Values LD0 PHIPTOC1 1 995 Str general START General start 1 Start 1 996 Str phsA phase A start 1 Start 1 997 Str phsB phase B start 1 Start 1 998 Str phsC phase C start 1 Start 1 99...

Page 24: ...OPERATE General operate 1 Operate 1 849 Op phsA phase A operate 1 Operate 1 850 Op phsB phase B operate 1 Operate 1 851 Op phsC phase C operate 1 Operate 2 3 8 LD0 DPHHPDOC1 Three phase directional ov...

Page 25: ...operate 1 Operate 2 3 11 LD0 EFIPTOC1 Non directional earth fault protection instantaneous stage 1 Table 13 LD0 EFIPTOC1 Non directional earth fault protection instantaneous stage 1 Object type Addr...

Page 26: ...tart 1 Start 1 810 Op general OPERATE General operate 1 Operate 2 3 15 LD0 INTRPTEF1 Intermittent earth fault protection 1 Table 17 LD0 INTRPTEF1 Intermittent earth fault protection 1 Object type Addr...

Page 27: ...fault protection 1 Object type Addr IEC 61850 name SA name Description Values LD0 WPSDE1 1 1331 Str general START General start 1 Start 1 1330 Op general OPERATE General operate 1 Operate 2 3 20 LD0 W...

Page 28: ...1 957 Op general OPERATE General operate 1 Operate 2 3 24 LD0 NSPTOC2 Negative sequence overcurrent protection 2 Table 26 LD0 NSPTOC2 Negative sequence overcurrent protection 2 Object type Addr IEC 61...

Page 29: ...Addr IEC 61850 name SA name Description Values LD0 PHPTUV1 1 1047 Str general START General start 1 Start 1 1048 Str phsA phase A start 1 Start 1 1049 Str phsB phase B start 1 Start 1 1050 Str phsC p...

Page 30: ...al OPERATE General operate 1 Operate 1 1060 Op phsA phase A operate 1 Operate 1 1061 Op phsB phase B operate 1 Operate 1 1062 Op phsC phase C operate 1 Operate 2 3 31 LD0 PHPTOV1 Phase overvoltage pro...

Page 31: ...t type Addr IEC 61850 name SA name Description Values LD0 PHPTOV3 1 1039 Str general START General start 1 Start 1 1040 Str phsA phase A start 1 Start 1 1041 Str phsB phase B start 1 Start 1 1042 Str...

Page 32: ...3 Op general OPR_OFRQ operate 1 Operate 1 LD0 FRPTUF1 Underfrequency 1 895 Op general OPR_UFRQ operate 1 Operate 1 LD0 FRPFRC2 Frequency gradient 1 877 Op general OPR_FRG operate 1 Operate 2 3 37 LD0...

Page 33: ...g bypass 1 Bypassed CTRL CBCSWI1 2 7001 Pos stVal POSITION Interm 0 Off 1 On 2 Bad 3 0 3 1 3003 Pos stSeld SELECTED CB selected 1 Selected CTRL CBCXCBR1 1 3004 BlkCls stVal BLK_CLOSE Close blocked 1 B...

Page 34: ...45 LD0 MAPGAPC1 Multipurpose protection signals 1 Object type Addr IEC 61850 name SA name Description Values LD0 MAPGAPC1 1 941 Str general Start 1 Start 1 940 Op general Operate 1 Operate 2 3 44 LD0...

Page 35: ...ion signals 6 Table 50 LD0 MAPGAPC6 Multipurpose protection signals 6 Object type Addr IEC 61850 name SA name Description Values LD0 MAPGAPC6 1 1344 Str general Start 1 Start 1 1342 Op general Operate...

Page 36: ...l Unbalance exceeds limit 1 Exceeds 2 3 53 CTRL DCSXSWI1 Disconnector position indication 1 Table 55 CTRL DCSXSWI1 Disconnector position indication 1 Object type Addr IEC 61850 name SA name Descriptio...

Page 37: ...LOCKED Lockout status 1 Lockout 1 2807 UnsRec stVal UNSUC_RECL Reclose fail status 1 Failed 1 2809 RdyRec stVal READY Ready reclose status 1 Ready 1 2810 ActRec stVal ACTIVE Active reclose status 1 A...

Page 38: ...RES_LO Low pressure lockout 1 Lockout 1 3077 SprChaAlm stVal SPR_CHR_ALM Spring charge time alarm 1 Alarm 2 3 60 LD0 TCSSCBR1 Trip circuit supervision 1 Table 62 LD0 TCSSCBR1 Trip circuit supervision...

Page 39: ...e 1 215 VDeaPhsA stVal U_A_AB_DEAD Low phsA or phsAB voltage 1 Low voltage 1 216 VDeaPhsB stVal U_B_BC_DEAD Low phsB or phsBC voltage 1 Low voltage 1 217 VDeaPhsC stVal U_C_CA_DEAD Low phsC or phsCA v...

Page 40: ...719 HiAlm stVal HIGH_ALARM High alarm 1 Alarm 1 4720 HiWrn stVal HIGH_WARN High warning 1 Warning 1 4721 LoAlm stVal LOW_ALARM Low alarm 1 Alarm 1 4722 LoWrn stVal LOW_WARN Low warning 1 Warning 2 3 6...

Page 41: ...Val Output 1 state 0 1 Off On 1 5091 SPCS02 stVal Output 2 state 0 1 Off On 1 5092 SPCS03 stVal Output 3 state 0 1 Off On 1 5093 SPCS04 stVal Output 4 state 0 1 Off On 1 5094 SPCS05 stVal Output 5 sta...

Page 42: ...n 1 5124 SPCS15 stVal Output 15 state 0 1 Off On 1 5125 SPCS16 stVal Output 16 state 0 1 Off On 2 3 73 LD0 SPCRGGIO1 Multipurpose binary output states 1 Table 75 LD0 SPCRGGIO1 Multipurpose binary outp...

Page 43: ...ate 0 1 Off On 1 5166 SPCS09 stVal Output 9 state 0 1 Off On 1 5167 SPCS10 stVal Output 10 state 0 1 Off On 1 5168 SPCS11 stVal Output 11 state 0 1 Off On 1 5169 SPCS12 stVal Output 12 state 0 1 Off O...

Page 44: ...GIO120 Physical I O states Table 79 LD0 XGGIO120 Physical I O states Object type Addr IEC 61850 name SA name Description Values LD0 XGGIO120 1 5010 Ind1 stVal Input 1 state 0 1 Off On 1 5011 Ind2 stVa...

Page 45: ..._ME_NC_1 14 M_ME_TC_1 1 2 36 M_ME_TF_1 2 3 21 Measurand normalized 9 M_ME_NA_1 10 M_ME_TA_1 1 2 34 M_ME_TD_1 2 3 22 Measurand scaled value 11 M_ME_NB_1 12 M_ME_TB_1 1 2 35 M_ME_TE_1 2 3 1 Requires set...

Page 46: ...iption Values LD0 T1PTTR1 20 10142 Tmp mag TEMP Object temperature 100 0 9999 9 C 20 10143 TmpRI mag TEMP_RL Relative temperature 0 00 99 99 C 21 10144 TmmsOp stVal THERMLEV_ST Est time to operate 0 6...

Page 47: ...Open travel time 0 60000 20 10141 TmsSprCha mag f Spring charge time 0 99 99 2 4 7 LD0 MDSOPT1 Generic operation time supervision 1 Table 87 LD0 MDSOPT1 Generic operation time supervision 1 Object typ...

Page 48: ...es LD0 VMMXU1 PhV Phase voltages 1 20 8047 cVal phsA mag U_INST_A phase A magnitude 0 5 00 xUn 20 8048 cVal phsB mag U_INST_B phase B magnitude 0 5 00 xUn 20 8049 cVal phsC mag U_INST_C phase C magnit...

Page 49: ...name Description Values LD0 VSMSQI2 20 8091 SeqA c1 instCVal mag U1_INST positive magnitude 0 5 00 xUn 20 8092 SeqA c2 instCVal mag U2_INST negative magnitude 0 5 00 xUn 20 8093 SeqA c3 instCVal mag U...

Page 50: ...Cnt stVal Fault record number 0 999999 20 12100 ProFcn stVal Protective function See the technical manual 20 12000 StrDur mag Start duration 0 100 00 20 12101 OpTm mag Operation time 0 000 999999 999...

Page 51: ...Seqb mag Zero seq voltage b 0 5 00 xUn 20 12067 VPsSeqb mag Positive seq voltage b 0 5 00 xUn 20 12068 VNgSeqb mag Negative seq voltage b 0 5 00 xUn 20 12047 MaxTmpRl mag Relative temperature 0 99 99...

Page 52: ...1 Three phase energy values 1 Object type Addr IEC 61850 name SA name Description Values LD0 PEMMTR1 30 14000 SupWh actVal Reverse active energy 0 1E10 Kwh 30 14001 SupVArh actVal Reverse reactive ene...

Page 53: ...G5 ctlVal Activate setting group 5 1 Activate 50 41006 ActSG6 ctlVal Activate setting group 6 1 Activate 2 6 3 CTRL Cxxxxx1 Circuit breaker control 1 Table 104 CTRL Cxxxxx1 Circuit breaker control 1 O...

Page 54: ...LD0 SRGAPC1 Multipurpose binary output flipflop resets 1 Object type Addr IEC 61850 name SA name Description Values LD0 SRGAPC1 50 21157 Rs1 ctlVal Reset flip flop 1 1 Reset 50 21158 Rs2 ctlVal Reset...

Page 55: ...0 1 Off On 50 21128 SPCS08 ctlVal Output 8 control 0 1 Off On 50 21129 SPCS09 ctlVal Output 9 control 0 1 Off On 50 21115 SPCS10 ctlVal Output 10 control 0 1 Off On 50 21116 SPCS11 ctlVal Output 11 c...

Page 56: ...SA name Description Values LD0 SPCRGGIO1 50 21252 SPCS01 ctlVal Output 1 control 0 1 Off On 50 21253 SPCS02 ctlVal Output 2 control 0 1 Off On 50 21254 SPCS03 ctlVal Output 3 control 0 1 Off On 50 212...

Page 57: ...tracted from the 60870 5 101 IEC 2003 Section 8 3 2 Interoperability IEC 60870 5 101 This companion standard presents sets of parameters and alternatives from which subsets have to be selected to impl...

Page 58: ...ble measured values 3 3 System or device System specific parameter indicate the station s function by marking one of the following with X System definition Controlling station definition master Contro...

Page 59: ...s 4800 bit s 4800 bit s 64000 bit s 300 bit s 9600 bit s 9600 bit s 600 bit s 19200 bit s 1200 bit s 38400 bit s 3 6 Link layer Network specific parameter mark all used options with an X Specify the...

Page 60: ...follows Type identification Cause of transmission A special assignment of ASDUs to class 2 messages is used as follows Type identification Cause of transmission In response to a class 2 poll a control...

Page 61: ...ith an X if it is only used in the standard direction R if only used in the reverse direction and B if used in both directions 1 Single point information M_SP_NA_1 2 Single point information with time...

Page 62: ...e tag CP56Time2a M_ST_TB_1 33 Bitstring of 32 bit with time tag CP56Time2a M_BO_TB_1 34 Measured value normalized value with time tag CP56Time2a M_ME_TD_1 35 Measured value scaled value with time tag...

Page 63: ...ecific parameter mark each Type ID with an X if it is only used in the standard direction R if only used in the reverse direction and B if used in both directions 100 Interrogation command C_IC_NA_1 1...

Page 64: ...ory select file call file call section F_SC_NA_1 123 Last section last segment F_LS_NA_1 124 Ack file ack section F_AF_NA_1 125 Segment F_SG_NA_1 126 Directory blank or X only available in monitor sta...

Page 65: ...s 1 2 3 4 5 6 7 8 9 10 11 12 13 20 to 36 37 to 41 44 45 46 47 1 M_SP_NA_1 X X X 2 M_SP_TA_1 X X 3 M_DP_NA_1 X X X 4 M_DP_TA_1 X X 5 M_ST_NA_1 6 M_ST_TA_1 7 M_BO_NA_1 8 M_BO_TA_1 9 M_ME_NA_1 X X X X 10...

Page 66: ...ct address 1 2 3 4 5 6 7 8 9 10 11 12 13 20 to 36 37 to 41 44 45 46 47 38 M_EP_TD_1 39 M_EP_TE_1 40 M_EP_TF_1 45 C_SC_NA_1 X X X X X X X X X 46 C_DC_NA_1 X X X X X X X X X 47 C_RC_NA_1 48 C_SE_NA_1 49...

Page 67: ...46 47 125 F_SG_NA_1 126 F_DR_TA_1 Blank or X only 3 8 Basic application functions Station initialization Station specific parameter mark with an X if the function is used Remote initialization Cyclic...

Page 68: ...led are defined in a project specific list Double point information M_DP_NA_1 M_DP_TA_1 and M_DP_TB_1 Step position information M_ST_NA_1 M_ST_TA_1 and M_ST_TB_1 Bitstring of 32 bit M_BO_NA_1 M_BO_TA_...

Page 69: ...ed in the reverse direction and B if used in both directions Direct command transmission Direct set point command transmission Select and execute command Select and execute set point command C_SE ACTT...

Page 70: ...an X if the function is only used in the standard direction R if only used in the reverse direction and B if used in both directions Threshold value Smoothing factor Low limit for transmission of mea...

Page 71: ...s of recorded analogue values File transfer in control direction Transparent file Background scan Station specific parameter mark with an X if the function is only used in the standard direction R if...

Page 72: ...66...

Page 73: ...01 Companion standard for basic telecontrol tasks IEC 60870 5 104 Network access for IEC 60870 5 101 IEC 60870 5 4 IED Intelligent electronic device LHMI Local human machine interface OC Overcurrent P...

Page 74: ...68...

Page 75: ...69...

Page 76: ...BB Oy Medium Voltage Products Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 Fax 358 10 22 41094 www abb com substationautomation 1MRS757824 C Copyright 2015 ABB All rig...