IEC 61850 name
AFL-Common SA name
Description
DPI value
FUN
INF
InUse
ASDU
GI
Coding
Phase overcurrent protection (2 stages)
LD0.PHIPTOC1.Str.phsA
-
Instanteous stage Start[.phsA]
10=Inst.Stage phsA start
162
34
0
2
1
1
LD0.PHIPTOC1.Str.phsB
-
Instanteous stage Start[.phsB]
10=Inst.Stage phsB start
162
35
0
2
1
1
LD0.PHIPTOC1.Str.phsC
-
Instanteous stage Start[.phsC]
10=Inst.Stage phsC start
162
36
0
2
1
1
LD0.PHLPTOC1.Str.phsA
-
Low stage Start[.phsA]
10=Low Stage phsA start
162
64
0
2
1
1
LD0.PHLPTOC1.Str.phsB
-
Low stage Start[.phsB]
10=Low Stage phsB start
162
65
0
2
1
1
LD0.PHLPTOC1.Str.phsC
-
Low stage Start[.phsC]
10=Low Stage phsC start
162
66
0
2
1
1
LD0.PHLPTOC1.Str.general
PHLPTOC1.START
Low stage Start[.general]
10=Low Stage start
162
84
1
2
1
1
LD0.PHLPTOC1.Op.general
PHLPTOC1.OPERATE
Low stage Operate[.general]
10=Low Stage operate
162
90
1
2
0
1
LD0.PHIPTOC1.Str.general
PHIPTOC1.START
Instanteous stage Start[.general]
10=Inst Stage start
162
97
1
2
1
1
LD0.PHIPTOC1.Op.general
PHIPTOC1.OPERATE
Instanteous stage Operate[.general]
10=Inst Stage operate
162
99
1
2
0
1
Directional earth-fault protection (1 stage)
LD0.DEFLPTOC1.Str.general
DEFLPDEF1.START
Low stage start
10=Low Stage start
163
84
1
2
1
1
LD0.DEFLPTOC1.Op.general
DEFLPDEF1.OPERATE
Low stage operate
10=Low Stage operate
163
90
1
2
0
1
Phase currents limit supervison
LD0.CMMXU1.HiAlm.stVal
CMMXU1.HIGH_ALARM
Phase currents High alarm
10=High alarm
210
1
0
1
1
1
LD0.CMMXU1.HiWrn.stVal
CMMXU1.HIGH_WARN
Phase currents High warning
10=High warning
210
2
0
1
1
1
LD0.CMMXU1.LoWrn.stVal
CMMXU1.LOW_WARN
Phase currents Low warning
10=Low warning
210
3
0
1
1
1
LD0.CMMXU1.LoAlm.stVal
CMMXU1.LOW_ALARM
Phase currents Low alarm
10=Low alarm
210
4
0
1
1
1
Residual current limit supervision
LD0.RESCMMXU1.HiAlm.stVal
RESCMMXU1.HIGH_ALAR M
Residual current High alarm
10=High alarm
210
11
0
1
1
1
LD0.RESCMMXU1.HiWrn.stVal
RESCMMXU1.HIGH_WARN
Residual current High warning
10=High warning
210
12
0
1
1
1
Phase-to-phase voltage limit supervision
LD0.VMMXU1.HiAlm.stVal
VMMXU1.HIGH_ALARM
Ph-Ph voltage High alarm
10=High alarm
211
1
0
1
1
1
LD0.VMMXU1.HiWrn.stVal
VMMXU1.HIGH_WARN
Ph-Ph voltage High warning
10=High warning
211
2
0
1
1
1
LD0.VMMXU1.LoWrn.stVal
VMMXU1.LOW_WARN
Ph-Ph voltage Low warning
10=Low warning
211
3
0
1
1
1
LD0.VMMXU1.LoAlm.stVal
VMMXU1.LOW_ALARM
Ph-Ph voltage Low alarm
10=Low alarm
211
4
0
1
1
1
Residual voltage limit supervision
LD0.RESVMMXU1.HiAlm.stVal
RESVMMXU1.HIGH_ALAR M
Residual voltage High alarm
10=High alarm
211
11
0
1
1
1
LD0.RESVMMXU1.HiWrn.stVal
RESVMMXU1.HIGH_WARN
Residual voltage High warning
10=High warning
211
12
0
1
1
1
Circuit breaker position and failure protection
CTRL.CBCILO1.EnaOpn.stVal
CBXCBR1.ENA_OPEN
CB open enabled
10=Open enabled
240
21
1
1
1
1
CTRL.CBCILO1.EnaCls.stVal
CBXCBR1.ENA_CLOSE
CB close enabled
10=Close enabled
240
22
1
1
1
1
CTRL.CBXCBR1.BlkOpn.stVal
CBXCBR1.BLK_OPEN
CB open blocked
10=Open blocked
240
23
1
1
1
1
CTRL.CBXCBR1.BlkCls.stVal
CBXCBR1.BLK_CLOSE
CB close blocked
10=Close blocked
240
24
1
1
1
1
CTRL.CBCILO1.ItlByPss.stVal
CBXCBR1.ITL_BYPASS
CB interlocking bypass
10=Interlocking bypassed
240
25
1
1
1
1
CTRL.CCBRBRF1.Str.general
CCBRBRF1.CB_FAULT_AL
CBFP Start, timer running
10=Start,timer running
240
101
0
2
1
1
Table continues on next page
Section 2
1MRS756882 B
IEC 60870-5-103 data mappings
16
REM615
Point List Manual