Table 148. Indications
Function
Value
Buffer capacity
Maximum number of indications presented for single disturbance
352
Maximum number of recorded disturbances
100
Table 149. Event recorder
Function
Value
Buffer capacity
Maximum number of events in disturbance report
150
Maximum number of disturbance reports
100
Resolution
1 ms
Accuracy
Depending on time
synchronizing
Table 150. Trip value recorder
Function
Value
Buffer capacity
Maximum number of analog inputs
30
Maximum number of disturbance reports
100
Table 151. Disturbance recorder
Function
Value
Buffer capacity
Maximum number of analog inputs
40
Maximum number of binary inputs
352
Maximum number of disturbance reports
100
Maximum total recording time (3.4 s recording time and maximum number of
channels, typical value)
340 seconds (100 recordings) at 50 Hz
280 seconds (80 recordings) at 60 Hz
Table 152. Event counter with limit supervision L4UFCNT
Function
Range or value
Accuracy
Counter value
0-65535
-
Max. count up speed
30 pulses/s (50% duty cycle)
-
Table 153. Running hour-meter TEILGAPC
Function
Range or value
Accuracy
Time limit for alarm supervision, tAlarm
(0 - 99999.9) hours
±0.1% of set value
Time limit for warning supervision, tWarning
(0 - 99999.9) hours
±0.1% of set value
Time limit for overflow supervision
Fixed to 99999.9 hours
±0.1%
1MRK 506 372-BEN -
Line distance protection REL670 2.2
Product version: 2.2
110