Name
Type
Values (Range)
Unit
Description
MAXPAFD
REAL
-
MW
Maximum forward active
power demand value for
set interval
MAXPARD
REAL
-
MW
Maximum reverse active
power demand value for
set interval
MAXPRFD
REAL
-
MVAr
Maximum forward
reactive power demand
value for set interval
MAXPRRD
REAL
-
MVAr
Maximum reactive power
demand value in reverse
direction
17.2.7
Operation principle
The instantaneous output values of active and reactive power from the Measurements
function CVMMXN are used and integrated over a selected time
tEnergy
to measure
shows the overall functionality of the energy
calculation and demand handling function ETPMMTR.
Zero Clamping
Detection
P
Q
Maximum Power
Demand Calculation
Energy Accumulation
Calculation
STARTACC
STOPACC
RSTDMD
MAXPAFD
MAXPARD
MAXPRFD
MAXPRRD
EAFALM
EARALM
ERFALM
ERRALM
EAFACC
EARACC
ERFACC
ERRACC
ACCINPRG
EAFPULSE
EARPULSE
ERFPULSE
ERRPULSE
RSTACC
IEC13000185-2-en.vsd
IEC13000185 V2 EN
Figure 456:
ETPMMTR Functional overview logical diagram
The integration of energy values is enabled by the setting
EnaAcc
and controlled by
the
STARTACC
and
STOPACC
inputs. If the integration is in progress, the output
ACCINPRG
is high. Otherwise, it is low. Figure
ACCINPRG
output.
ACCINPRG
is active when the
STARTACC
input is active and the
EnaAcc
setting is enabled. When the
RSTACC
input is in the active state, the output
ACCINPRG
is low even if the integration of energy is enabled.
ACCINPRG
is
deactivated by activating the
STOPACC
input.
1MRK502052-UEN B
Section 17
Metering
989
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...