Name
Values (Range)
Unit
Step
Default
Description
CLFactor
1.0 - 3.0
-
0.1
2.0
Adjustable factor for contact life function
InitCLCounter
0 - 9999999
s
1
250000
CL counter start value
EnabTapCmd
Off
On
-
-
On
Enable commands to tap changer
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
14.4.8
Monitored data
Table 445:
TCMYLTC Monitored data
Name
Type
Values (Range)
Unit
Description
CNT_VAL
INTEGER
-
-
Number of operations on
tap changer
CLCNT_VAL
REAL
-
-
Remaining number of
operations at rated load
TCPOS
INTEGER
-
-
Integer value
corresponding to actual
tap position
Table 446:
TCLYLTC Monitored data
Name
Type
Values (Range)
Unit
Description
TCPOS
INTEGER
-
-
Integer value
corresponding to actual
tap position
14.4.9
Operation principle
The voltage control function is built up by two function blocks. Both are logical nodes
in IEC 61850-8-1.
•
Automatic voltage control for tap changer
•
TR1ATCC for single control
•
TR8ATCC for parallel control
•
Tap changer control and supervision
•
TCMYLTC, 6 binary inputs
•
TCLYLTC, 32 binary inputs
TR1ATCCand TR8ATCC are designed to automatically maintain the voltage at the
LV-side side of a power transformer within given limits around a set target voltage. A
raise or lower command is generated whenever the measured voltage, for a given
period of time, deviates from the set target value by more than the preset deadband
value that is, degree of insensitivity. A time-delay (inverse or definite time) is set to
Section 14
1MRK502052-UEN B
Control
758
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...