Table 438:
TCLYLTC Output signals
Name
Type
Description
URAISE
BOOLEAN
Raise voltage command to tap changer
ULOWER
BOOLEAN
Lower voltage command to tap changer
HIPOSAL
BOOLEAN
Alarm for tap in highest volt position
LOPOSAL
BOOLEAN
Alarm for tap in lowest volt position
POSERRAL
BOOLEAN
Alarm that indicates a problem with the position
indication
CMDERRAL
BOOLEAN
Alarm for a command without an expected position
change
TCERRAL
BOOLEAN
Alarm for none or illegal tap position change
POSOUT
BOOLEAN
Tap position outside min and max position
CONVERR
BOOLEAN
General tap position conversion error
NEWPOS
BOOLEAN
A new tap position is reported, 1 sec pulse
HIDIFPOS
BOOLEAN
Tap position has changed more than one position
INVALPOS
BOOLEAN
Last position change was an invalid change
CNT_VAL
INTEGER
Number of operations on tap changer
TCPOS
INTEGER
Integer value corresponding to actual tap position
YLTCOUT
GROUP SIGNAL
Group connection to ATCCIN
Table 439:
VCTRRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
Table 440:
VCTRRCV Output signals
Name
Type
Description
VCTR_REC
GROUP SIGNAL
Received data from horizontal communication
COMVALID
BOOLEAN
Communication is valid
DATVALID
BOOLEAN
Data valid
14.4.7
Settings
Table 441:
TCMYLTC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
tTCTimeout
1 - 120
s
1
5
Tap changer constant time-out
tPulseDur
0.5 - 10.0
s
0.1
1.5
Raise/lower command output pulse
duration
Section 14
1MRK502052-UEN B
Control
756
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...