14.2.12.4
Logic diagram
POS_EVAL
POSITION
OPENPOS
CLOSEPOS
IEC08000469-1-en.vsd
Position including quality
Open/close position of
switch device
IEC08000469-1-EN V1 EN
Only the value, open/close, and status is used in this function. Time information is not
used.
Input position (Value)
Signal quality
Output OPENPOS
Output CLOSEPOS
0 (Breaker
intermediate)
Good
0
0
1 (Breaker open)
Good
1
0
2 (Breaker closed)
Good
0
1
3 (Breaker faulty)
Good
0
0
Any
Invalid
0
0
Any
Oscillatory
0
0
14.2.12.5
Signals
Table 395:
POS_EVAL Input signals
Name
Type
Default
Description
POSITION
INTEGER
0
Position status including quality
Table 396:
POS_EVAL Output signals
Name
Type
Description
OPENPOS
BOOLEAN
Open position
CLOSEPOS
BOOLEAN
Close position
14.3
Apparatus control APC
14.3.1
Functionality
The apparatus control functions are used for control and supervision of circuit
breakers, disconnectors and earthing switches within a bay. Permission to operate is
given after evaluation of conditions from other functions such as interlocking,
synchrocheck, operator place selection and external or internal blockings.
Apparatus control features:
Section 14
1MRK502052-UEN B
Control
704
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...