7.6.3
Function block
OOSPPAM
I3P1*
I3P2*
U3P*
BLOCK
BLKGEN
BLKMOT
EXTZ1
TRIP
TRIPZ1
TRIPZ2
START
GENMODE
MOTMODE
R
X
SLIPFREQ
ROTORANG
UCOSPHI
IEC12000188-3-en.vsd
IEC12000188 V3 EN
Figure 110:
OOSPPAM function block
7.6.4
Signals
Table 106:
OOSPPAM Input signals
Name
Type
Default
Description
I3P1
GROUP
SIGNAL
-
Group connection for three-phase current input 1
I3P2
GROUP
SIGNAL
-
Group connection for three-phase current input 2
U3P
GROUP
SIGNAL
-
Group connection for three-phase voltage input
BLOCK
BOOLEAN
0
Block of function
BLKGEN
BOOLEAN
0
Block operation in generating direction
BLKMOT
BOOLEAN
0
Block operation in motor direction
EXTZ1
BOOLEAN
0
Extension of zone1 reach to zone2 settings
Table 107:
OOSPPAM Output signals
Name
Type
Description
TRIP
BOOLEAN
Common trip, issued when either zone 1 or zone 2
give trip
TRIPZ1
BOOLEAN
Zone 1 trip
TRIPZ2
BOOLEAN
Zone 2 trip
START
BOOLEAN
Set when measured impedance enters lens
characteristic
GENMODE
BOOLEAN
Generator rotates faster than the system during
pole slip
MOTMODE
BOOLEAN
Generator rotates slower than the system during
pole slip
R
REAL
Real part of measured positive-sequence
impedance % of UBase/(sqrt(3)*IBase)
X
REAL
Imaginary part of measured positive-seq
impedance % of UBase/(sqrt(3)*IBase)
Table continues on next page
Section 7
1MRK502052-UEN B
Impedance protection
260
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...