7.5.6
Monitored data
Table 104:
PSPPPAM Monitored data
Name
Type
Values (Range)
Unit
Description
SFREQ
REAL
-
Hz
Slip frequency
SLIPZOHM
REAL
-
Ohm
Slip impedance in ohms
SLIPZPER
REAL
-
%
Slip impedance in
percent of ZBase
UCOS
REAL
-
kV
UCosPhi voltage
UCOSPER
REAL
-
%
UCosPhi voltage in
percent of UBase
7.5.7
Operation principle
If the generator is faster than the power system, the rotor movement in the impedance
and voltage diagram is from right to left and generating is signaled. If the generator is
slower than the power system, the rotor movement is from left to right and motoring
is signaled (the power system drives the generator as if it were a motor).
The movements in the impedance plane can be seen in Figure
. The transient
behavior is described by the transient EMF's E
A
and E
B
, and by X'
d
, X
T
and the
transient system impedance Z
S
.
1MRK502052-UEN B
Section 7
Impedance protection
255
Technical manual