Table 936:
Auxiliary power supply and binary I/O connectors
Connector type
Rated voltage
Maximum conductor area
Screw compression type
250 V AC
2.5 mm
2
(AWG14)
2 × 1 mm
2
(2 x AWG18)
Terminal blocks suitable for
ring lug terminals
300 V AC
3 mm
2
(AWG14)
Because of limitations of space, when ring lug terminal is ordered for
Binary I/O connections, one blank slot is necessary between two
adjacent IO cards. Please refer to the ordering particulars for details.
21.5.4
Influencing factors
Table 937:
Temperature and humidity influence
Parameter
Reference value
Nominal range
Influence
Ambient temperature,
operate value
+20°C
-10 °C to +55°C
0.02% / °C
Relative humidity
Operative range
10%-90%
0%-95%
10%-90%
-
Storage temperature
-
-40 °C to +70 °C
-
Table 938:
Auxiliary DC supply voltage influence on functionality during operation
Dependence on
Reference value
Within nominal range Influence
Ripple, in DC auxiliary voltage
Operative range
max. 2%
Full wave rectified
15% of EL
0.01% / %
Auxiliary voltage dependence, operate
value
±20% of EL
0.01% / %
Interrupted auxiliary DC voltage
24-60 V DC ± 20%
90-250 V DC
±
20%
Interruption
interval
0–50 ms
No restart
0–∞ s
Correct
behaviour at
power down
Restart time
<300 s
Section 21
1MRK502052-UEN B
IED hardware
1216
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...