Table 825:
Pre-defined user types
Access rights
Guest
Super User
SPA Guest
System
Operator
Protection
Engineer
Design
Engineer
User
Administrator
Basic setting possibilities (change
setting group, control settings, limit
supervision)
R
R/W
R
R/W
R/W
R/W
R
Advanced setting possibilities (for
example protection settings)
R
R/W
R
R
R/W
R/W
R
Basic control possibilities (process
control, no bypass)
R
R/W
R/W
R/W
R/W
R/W
R
Advanced control possibilities
(process control including interlock
trigg)
R
R/W
R/W
R/W
R/W
R/W
R
Basic command handling (for
example clear LEDs, manual trigg)
R
R/W
R
R/W
R/W
R/W
R
Advanced command handling (for
example clear disturbance record)
R
R/W
R
R
R/W
R/W
R/W
Basic configuration possibilities
(I/O-configuration in SMT)
R
R/W
R
R
R
R/W
R/W
Advanced configuration
possibilities (application
configuration including SMT, GDE
and CMT)
R
R/W
R
R
R
R/W
R/W
File loading (database loading from
XML-file)
-
R/W
-
-
-
R/W
R/W
File dumping (database dumping to
XML-file)
-
R/W
-
-
-
R/W
R/W
File transfer (FTP file transfer)
-
R/W
-
R/W
R/W
R/W
R/W
File transfer (limited) (FTP file
transfer)
R
R/W
R
R/W
R/W
R/W
R/W
File Transfer (SPA File Transfer)
-
R/W
-
-
-
R/W
-
Database access for normal user
R
R/W
R
R/W
R/W
R/W
R/W
User administration (user
management – FTP File Transfer)
R
R/W
R
R
R
R
R/W
User administration (user
management – SPA File Transfer)
-
R/W
-
-
-
-
-
The IED users can be created, deleted and edited only with the IED User Management
within PCM600. The user can only LogOn or LogOff on the local HMI on the IED,
there are no users, groups or functions that can be defined on local HMI.
If the IED is Central Account Management enabled, users can only be
created, deleted or edited in the Central Account Management server.
In that case, only the user rights can be edited using the PCM600 tool.
See Cyber Security Deployment Guidelines manual.
Only characters A - Z, a - z and 0 - 9 should be used in user names and
passwords.
1MRK502052-UEN B
Section 20
Basic IED functions
1091
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...