Table 11: Specification of the fiber optic connectors
Glass fiber
Plastic fiber
Cable connector
ST-connector
snap-in connector
Cable diameter
62.5/125 m
1 mm
Max. cable length
1000 m
10 m
Wavelength
820-900 nm
660 nm
Transmitted power
-13 dBm (HFBR-1414)
-13 dBm (HFBR-1521)
Receiver sensitivity
-24 dBm (HFBR-2412)
-20 dBm (HFBR-2521)
9.1.2
The LON Protocol
M14804-32 v2
The LON protocol is specified in the LonTalkProtocol Specification Version 3 from Echelon
Corporation. This protocol is designed for communication in control networks and is a peer-
to-peer protocol where all the devices connected to the network can communicate with each
other directly. For more information of the bay-to-bay communication, refer to the section
Multiple command function.
9.1.3
Hardware and software modules
M14804-35 v4
The hardware needed for applying LON communication depends on the application, but one
very central unit needed is the LON Star Coupler and optical fibers connecting the star coupler
to the IEDs. To interface the IEDs from the MicroSCADA with Classic Monitor, application
library LIB520 is required.
The HV Control 670 software module is included in the LIB520 high-voltage process package,
which is a part of the Application Software Library in MicroSCADA applications.
The HV Control 670 software module is used for control functions in the IEDs. The module
contains a process picture, dialogues and a tool to generate a process database for the
control application in MicroSCADA.
When using MicroSCADA Monitor Pro instead of the Classic Monitor, SA LIB is used together
with 670 series Object Type files.
The HV Control 670 software module and 670 series Object Type files are used
with both 650 and 670 series IEDs.
Use the LON Network Tool (LNT) to set the LON communication. This is a software tool
applied as one node on the LON bus. To communicate via LON, the IEDs need to know
•
The node addresses of the other connected IEDs.
•
The network variable selectors to be used.
This is organized by LNT.
The node address is transferred to LNT via the local HMI by setting the parameter
ServicePinMsg = Yes. The node address is sent to LNT via the LON bus, or LNT can scan the
network for new nodes.
The communication speed of the LON bus is set to the default of 1.25 Mbit/s. This can be
changed by LNT.
Section 9
1MRK 502 067-UEN B
Establishing connection and verifying the LON communication
80
Commissioning manual