Section 16
Protection relay and functionality tests
Table 479:
Electromagnetic compatibility tests
Description
Requirement
Reference
1 MHz/100 kHz burst disturbance
test, all ports
IEC60255-22-1, Class III
IEC61000-4-18
IEEE37.90.1-2002
•
Differential mode
±2.5 kV
•
Common mode
±2.5 kV
3 MHz/10 MHz/30 MHz burst
disturbance test, all ports
IEC61000-4-18, Level 3
•
Common mode
±2.5 kV
Fast transient disturbance test, all
ports
IEC60255-22-4, Class A
IEC61000-4-4
IEEE37.90.1-2002
•
Common mode/differential
mode
±4 kV
Radio frequency interference
tests
10 V/m (prior to modulation)
f = 80...2700 MHz (sweep and
keying test)
IEC60255-22-3
IEC61000-4-3
20 V/m (prior to modulation)
f = 80...1000 MHz (sweep and
keying test)
IEEE C37.90.2-2004
Electrostatic discharge test
IEC60255-22-2
IEC61000-4-2, Class 4
IEEE C37.90.3-2001
•
Contact discharge
±8 kV
•
Air discharge
±15 kV
Surge immunity test
IEC 61000-4-5
IEC 60255-22-5
•
Communication
1 kV, line-to-earth
•
Other ports
4 kV, line-to-earth
2 kV, line-to-line
Power frequency magnetic field
300 A/m, >300 s
1000 A/m, 3 s
IEC 61000-4-8
Voltage dips and short
interruptions
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11
Power frequency immunity test,
binary inputs
150 V
rms
, differential mode
300 V
rms
, common mode
IEC 61000-4-16
IEC 60255-22-7, class A
Table continues on next page
1MRS240050-IB C
Section 16
Protection relay and functionality tests
REF615R
647
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...