Table 345:
PQVPH Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm signal for THD
8.2.7
Settings
Table 346:
PQVPH Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Demand interval
0=1 minute
1=5 minutes
2=10 minutes
3=15 minutes
4=30 minutes
5=60 minutes
6=180 minutes
2=10 minutes
Time interval for demand calculation
Demand window
1=Sliding
2=Non-sliding
1=Sliding
Demand calculation window type
THD alarm limit
1.0...100.0
%
0.1
50.0
THD alarm limit
8.2.8
Monitored data
Table 347:
PQVPH Monitored data
Name
Type
Values (Range)
Unit
Description
Max demand THD
VA
FLOAT32
0.00...500.00
%
Maximum demand THD for
phase A
Max demand THD
VB
FLOAT32
0.00...500.00
%
Maximum demand THD for
phase B
Max demand THD
VC
FLOAT32
0.00...500.00
%
Maximum demand THD for
phase C
Time max dmd THD
VA
Timestamp
Time of maximum demand
THD phase A
Time max dmd THD
VB
Timestamp
Time of maximum demand
THD phase B
Time max dmd THD
VC
Timestamp
Time of maximum demand
THD phase C
3SMHTHD_A
FLOAT32
0.00...500.00
%
3 second mean value of THD
for phase A
DMD_THD_A
FLOAT32
0.00...500.00
%
Demand value for THD for
phase A
3SMHTHD_B
FLOAT32
0.00...500.00
%
3 second mean value of THD
for phase B
Table continues on next page
1MRS240050-IB C
Section 8
Power quality measurement functions
REF615R
419
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...