If the measured data is within parentheses, there are some problems to
express the data.
7.1.2
Measurement functionality
The functions can be enabled or disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
Some of the measurement functions operate on two alternative measurement modes:
"DFT" and "RMS". The measurement mode is selected with the
X Measurement mode
setting. Depending on the measuring function if the measurement mode cannot be
selected, the measuring mode is "DFT".
Demand value calculation
The demand values are calculated separately for each measurement function and per
phase when applicable. The available measurement modes are "Linear" and
"Logarithmic". The "Logarithmic" measurement mode is only effective for phase current
and residual current demand value calculations. The demand value calculation mode is
selected with the setting parameter
Configuration/Measurements/A demand Av mode
.
The time interval for all demand value calculations is selected with the setting parameter
Configuration/Measurements/Demand interval
.
If the
Demand interval
setting is set to "15 minutes", for example, the demand values are
updated every quarter of an hour. The demand time interval is synchronized to the real-
time clock of the protection relay. When the demand time interval or calculation mode is
changed, it initializes the demand value calculation. For the very first demand value
calculation interval, the values are stated as invalid until the first refresh is available.
The "Linear" calculation mode uses the periodic sliding average calculation of the
measured signal over the demand time interval. A new demand value is obtained once in
a minute, indicating the analog signal demand over the demand time interval proceeding
the update time. The actual rolling demand values are stored in the memory until the value
is updated at the end of the next time interval.
The "Logarithmic" calculation mode uses the periodic calculation using a log10 function
over the demand time interval to replicate thermal demand ammeters. The logarithmic
demand calculates a snapshot of the analog signal every 1/15 x demand time interval.
Each measurement function has its own recorded data values. In protection relay, these are
found in
Monitoring/Recorded data/Measurements
. In the technical manual these are
listed in the monitored data section of each measurement function. These values are
periodically updated with the maximum and minimum demand values. The time stamps
are provided for both values.
Section 7
1MRS240050-IB C
Measurement functions
384
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...