Parameter
Values (Range)
Unit
Step
Default
Description
Change rate enable
0=False
1=True
0=False
Enabling operation of change based function
Min Op voltage delta
0.01...1.00
xUn
0.01
0.70
Minimum trip level of phase voltage for delta
calculation
Min Op current delta
0.01...1.00
xIn
0.01
0.10
Minimum trip level of phase current for delta
calculation
Seal in voltage
0.01...1.00
xUn
0.01
0.70
Trip level of seal-in phase voltage
Enable seal in
0=False
1=True
0=False
Enabling seal in functionality
Current dead Lin Val
0.05...1.00
xIn
0.01
0.05
Trip level for open phase current detection
6.3.8
Monitored data
Table 289:
60 Monitored data
Name
Type
Values (Range)
Unit
Description
60
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
6.3.9
Technical data
Table 290:
60 Technical data
Characteristic
Value
Trip time
1)
NPS function
V
Fault
= 1.1 × set
Neg
Seq voltage Lev
<33 ms
V
Fault
= 5.0 × set
Neg
Seq voltage Lev
<18 ms
Delta function
ΔV = 1.1 × set
Voltage
change rate
<30 ms
ΔV = 2.0 × set
Voltage
change rate
<24 ms
1) Includes the delay of the signal output contact, f
n
= 60 Hz, fault voltage with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
1MRS240050-IB C
Section 6
Supervision functions
REF615R
377
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...