6.3.2
Function block
GUID-0A336F51-D8FA-4C64-A7FE-7A4270E621E7-ANSI V1 EN
Figure 196:
Function block
6.3.3
Functionality
The fuse failure supervision function 60 is used to block the voltage-measuring functions
when failure occurs in the secondary circuits between the voltage transformer (or combi
sensor or voltage sensor) and protection relay to avoid faulty operation of the voltage
protection functions.
60 has two algorithms, a negative sequence-based algorithm and a delta current and delta
voltage algorithm.
A criterion based on the delta current and the delta voltage measurements can be activated
to detect three-phase fuse failures which usually are more associated with the voltage
transformer switching during station operations.
6.3.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The operation of 60 can be described with a module diagram. All the modules in the
diagram are explained in the next sections.
1MRS240050-IB C
Section 6
Supervision functions
REF615R
371
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...