The function contains a blocking functionality. Blocking deactivates all outputs and resets
timers.
5.5.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The operation of AFD can be described by using a module diagram. All the modules in the
diagram are explained in the next sections.
TRIP
Level
detector
1
I_A
I_B
I_C
BLOCK
Level
detector
2
I_G
FLT_ARC
REM_FLT_ARC
ARC_FLT_DET
Operation
mode
selector
t
Dropoff
OPR_MODE
t
Dropoff
A070746-ANSI V2 EN
Figure 172:
Functional module diagram
Level detector 1
The measured phase currents are compared phasewise to the set
Phase pickup value
. If the
measured value exceeds the set
Phase pickup value
, the level detector reports the
exceeding of the value to the operation mode selector.
Level detector 2
The measured ground currents are compared to the set
Ground pickup value
. If the
measured value exceeds the set
Ground pickup value
, the level detector reports the
exceeding of the value to the operation mode selector.
Operation mode selector
Depending on the
Operation mode
setting, the operation mode selector makes sure that all
required criteria are fulfilled for a reliable decision of an arc fault situation. The user can
select either "Light+current", "Light only" or "BI controlled" operation mode. The
operation is based on both current and light information in “Light+current” mode, on light
information only in “Light only” mode or on remotely controlled information in “BI
controlled” mode. When the "BI controlled" mode is in use and the
OPR_MODE
input is
Section 5
1MRS240050-IB C
Protection-related functions
338
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...