enable restart time
Ena restart level
Cooling time
=
−
⋅
100
100
GUID-8C676DA9-F90A-46B6-9A24-9D74C52DE442 V1 EN
(Equation 7)
If the excitation level increases above the set value when
BLK_RESTART
is active, the
TRIP
output is activated immediately.
If the excitation level increases above the set value when
BLK_RESTART
is not active but
COOL_ACTIVE
is active, the
TRIP
output is not activated instantly. In this case, the
remaining part of the cooling timer affects the calculation of the operation timer as shown
in
. This compensates for the heating effect and makes the overall trip time
shorter.
GUID-E62B7A83-72F7-4489-B7BC-DE30D26BF6C7 V1 EN
Figure 122:
Example of an inverse time counter operation if
TRIP
occurs when
BLK_RESTART
is inactive while
COOL_ACTIVE
is active. The Restart
Ena level setting is considered to be 40 percent.
4.2.5.6
Application
If the laminated core of a power transformer or generator is subjected to a magnetic flux
density beyond its designed limits, the leakage flux increases. This results in a heavy
hysteresis and eddy current losses in the non-laminated parts. These losses can cause
excessive heating and severe damage to the insulation and adjacent parts in a relatively
short time.
1MRS240050-IB C
Section 4
Protection functions
REF615R
255
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...