Table 73:
50P-3 Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
ENA_MULT
BOOLEAN
0=False
Enable signal for current multiplier
Table 74:
51P Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
Table 75:
50P-1/2 Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
Table 76:
50P-3 Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
4.1.1.9
Settings
Table 77:
51P Group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value
0.05...5.00
xIn
0.01
0.05
Pickup value
Pickup value mult
0.8...10.0
0.1
1.0
Multiplier for scaling the pickup value
Time multiplier
0.05...15.00
0.01
1.00
Time multiplier in IEC/ANSI IDMT curves
Table continues on next page
Section 4
1MRS240050-IB C
Protection functions
126
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...