RefSource
: This setting is used to select the reference source between input and setting
for comparison.
•
Input REF
: The function will take reference value from input REF
•
Set Value
: The function will take reference value from setting
SetValue
SetValue
: This setting is used to set the reference value for comparison when setting
RefSource
is selected as
SetValue
.
16.13.4
Setting example
GUID-13302FD6-1585-42FE-BD6D-44F231982C59 v2
For absolute comparison between inputs:
Set the
EnaAbs
=
Absolute
Set the
RefSource
=
Input REF
Similarly for Signed comparison between inputs
Set the
EnaAbs
=
Signed
Set the
RefSource
=
Input REF
For absolute comparison between input and setting
Set the
EnaAbs
=
Absolute
Set the
RefSource
=
Set Value
SetValue
shall be set between -2000000000 to 2000000000
Similarly for signed comparison between input and setting
Set the
EnaAbs
=
Signed
Set the
RefSource
=
Set Value
SetValue
shall be set between -2000000000 to 2000000000
1MRK 511 401-UUS A
Section 16
Logic
Bay control REC670 2.2 ANSI
505
Application manual