Table 32:
Type of reclosing shots at different settings of ARMode or integer inputs to MODEINT
MODEINT (integer)
ARMode
Type of fault
1st shot
2nd-5th shot
1
3ph
1ph
3ph
3ph
2ph
3ph
3ph
3ph
3ph
3ph
2
1/2/3ph
1ph
1ph
3ph
2ph
2ph
3ph
3ph
3ph
3ph
3
1/2ph
1ph
1ph
3ph
2ph
2ph
3ph
3ph
.....
.....
4
1ph + 1*2ph
1ph
1ph
3ph
2ph
2ph
.....
3ph
.....
.....
5
1/2ph + 1*3ph
1ph
1ph
3ph
2ph
2ph
3ph
3ph
3ph
.....
6
1ph + 1*2/3ph
1ph
1ph
3ph
2ph
2ph
.....
3ph
3ph
.....
A start of a new auto reclosing cycle during the set “reset time” is blocked when the set
number of reclosing shots have been reached.
14.2.2.14
External selection of auto reclosing mode
M12391-241 v5
The auto reclosing mode can be selected by use of available logic function blocks.
Below is an example where the choice of mode,
ARMode
=
3ph
or
ARMode
=
1/2/3ph
, is
done from a hardware function key at the front of the IED, but alternatively there can
for example, be a physical selector switch on the front of the panel which is connected
to a binary to integer function block (BTIGAPC).
The connection example for selection of the auto reclosing mode is shown in Figure
.
Section 14
1MRK 511 401-UUS A
Control
332
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...