Characteristx
: Selection of time characteristic for step
x
. Definite time delay and
different types of inverse time characteristics are available according to Table
Table 19:
Inverse time characteristics
Curve name
ANSI Extremely Inverse
ANSI Very Inverse
ANSI Normal Inverse
ANSI Moderately Inverse
ANSI/IEEE Definite time
ANSI Long Time Extremely Inverse
ANSI Long Time Very Inverse
ANSI Long Time Inverse
IEC Normal Inverse
IEC Very Inverse
IEC Inverse
IEC Extremely Inverse
IEC Short Time Inverse
IEC Long Time Inverse
IEC Definite Time
User Programmable
ASEA RI
RXIDG or RD (logarithmic)
The different characteristics are described in
Technical manual
.
Pickupx
: Operate phase current level for step
x
given in % of
IB
.
Ix>Max
and
Ix>Min
should only be changed if remote setting of operation current
level,
Ix>
, is used. The limits are used for decreasing the used range of the
Ix>
setting.
If
Ix>
is set outside
Ix>Max
and
Ix>Min
, the closest of the limits to
Ix>
is used by the
function. If
Ix>Max
is smaller than
Ix>Min
, the limits are swapped.
tx
: Definite time delay for step
x
. The definite time
tx
is added to the inverse time when
inverse time characteristic is selected. Note that the value set is the time between
activation of the start and the trip outputs.
TDx
: Time multiplier for inverse time delay for step
x
.
IMinx
: Minimum operate current in % of
IB
for all inverse time characteristics, below
which no operation takes place.
1MRK 511 401-UUS A
Section 8
Current protection
Bay control REC670 2.2 ANSI
157
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...